CFL vertical pump does not water failure causes and solutions: 1, import and export valves are not open, out of the pipeline blockage, runner blockage. ★ check, remove the blockage. 2, the motor is running in the wrong direction, the motor phase loss, the number of revolutions is very slow. ★ adjust the motor direction, tighten the motor wiring. 3, suction tube leakage. ★ tighten the sealing surface, remove the air. 4, the pump is not filled with liquid, the pump cavity with air. ★ Open the pump cover or open the exhaust valve, exhaust air. 5, imported water supply, suction is high, the valve leakage. ★ stop, check, adjust (grid connection and suction with the use of easy to appear) 6, pipe resistance is too large, improper pump selection. ★ reduce the pipe bend, re-select the pump. More Search Keywords: Pumps
China Built In Gas Oven,Gas Oven,Gas Stove Oven Supplier
for this kind of goods ,we use good quality stainless steel with high quality gas stove owen .
China Built In Gas Oven,Gas Oven supplier & manufacturer, offer low price, high quality Gas Stove Oven,Gas Oven With Stove, etc.
We support like this kind of goods to different coutnry for more than 20 years ,we had good experience .with good quality and competition price .
Built In Gas Oven,Gas Oven,Gas Stove Oven,Gas Oven With Stove
Gas Oven,stove tops,gas pizza oven,gas range stove,dual fuel range Vast Dragon Trading Limited , https://www.standingoven.com