Jiangsu Ankerui Electric Appliance Manufacturing Co., Ltd. Jiangyin , Jiangsu 214405

Abstract Ankerui residual current type Lu Xiaojun electrical fire monitoring system adopts ARCM residual current type electrical fire monitoring device. It adopts on-site local networking method. After networking, it communicates via field bus and transmits to the background remotely to use for shopping malls and hotels. Low-voltage power distribution systems such as airports, banks, hospitals, and factories are used for electrical fire monitoring. This article focuses on the structure of the Acrel-6000 electrical fire monitoring system, the equipment involved, the functions achieved, and its significance through the introduction of the electrical fire monitoring system project of the First People's Hospital of Tianshui.

Key words: fire detector; electrical fire; Tianshui First People's Hospital; Acrel-6000; tertiary A hospital;

0 Foreword

First People's Hospital of Tianshui City, the former outpatient waiting hall floor is small, poor treatment process, has seriously hampered the development of the hospital, to sustainable development, invested 150 million yuan new Emergency Department Building, with a total construction area of 45,340 square meters, a total of The 20th floor integrates outpatient, emergency, ward and underground parking.

This project is a fire monitoring system for the emergency building at the First People's Hospital of Tianshui City. The monitoring scope is mainly for the low-voltage power distribution room in the basement and the power distribution cabinet in each floor.

Acrel-6000 fire monitoring takes full advantage of the latest developments in modern electronic technology, computer technology, network technology, and fieldbus technology, and performs distributed data collection and centralized monitoring and management of the power distribution system. The secondary equipment of the distribution system is networked. Through the computer and the communication network, the field devices of the decentralized power distribution station are connected into an organic whole, and remote monitoring and centralized management of the power grid operation are realized.

The system can effectively predict and monitor the leakage and leakage due to leakage , and can accurately monitor the fault and abnormal state of the electrical circuit. It can discover the fire hazards of the electrical fire and promptly remind the personnel to eliminate these hidden troubles. It helps enterprises to save labor costs and improve work efficiency.

1 System Requirements Analysis

Detection of leakage current, over current, over temperature and other signals, sound and light signal alarm, accurately report the fault line address, monitor the changes in the point of failure. Store various fault and operation test signals to show system power status.

2 Reference standards

The system complies with the People's Republic of China national standard GB14287.1-2005 "Electrical fire monitoring system Part 1: Electrical fire monitoring equipment."

3 system structure

Acrel- 6 000 electrical fire monitoring system is a company independently researched and developed for receiving residual current type electrical fire detectors and other field equipment signals to realize the alarm, monitoring, control, and management of protected electrical circuits running on computers. Level hardware/software system. This system is applied to fire control centers in large shopping malls, living quarters, production bases, office buildings, shopping malls and hotels, and remotely measures, remotely adjusts, remotely controls, and remotely detects the detectors scattered in buildings to facilitate monitoring and management. The system uses a standard Modbus field bus to connect detectors with communication functions. When the detected parameters in the field protection circuit exceed the alarm setting value, it can send alarm signals, control signals, can indicate alarm locations and save alarms. information.

The main equipment of Acrel- 6 000 /Q100 electrical fire monitoring system is as follows:

l Computer: Industrial PC, C ore 2 2.66G/1G/320G+ keyboard and mouse 17 " LCD monitor, W indows XP , A crel-6000 electrical fire monitoring system software;

l Input and output modules: Built-in ARTU remote intelligent I/O modules developed by the company;

l sound and light alarm: built-in five-tone signal speaker, LED indicator, silence button;

l Standby power: built-in 1 kVA on-line long-term UPS.

l host panel components layout and function description

1: Alarm indicator (red), the indicator lights up when the system receives the monitoring alarm signal.

2: Fault indicator (yellow), the indicator lights up when the system receives a fault alarm signal.

3: Running indicator (green). The indicator is on when the system is operating normally.

4: Main power indicator (white). Lights when the main power supply is used.

5: Standby power indicator (white). Lights up when using standby power.

6: Mute button (black) to eliminate and restore the alarm sound.

7: Manually output button (black), manually start the control output of the protected circuit under alarm state.

The distribution of this system mainly uses a computer distribution network structure.

1) Station control management

Station management The management personnel of the electrical fire monitoring system are the direct windows of human-computer interaction and the top part of the system. Mainly by the system software and necessary hardware equipment, such as monitoring host, display, UPS power supply and other components. The monitoring system software calculates, analyzes, and processes various types of data on the site, and responds to the on-site operations by means of graphics, digital display, sound, and indicator lights.

Monitoring host: used for data acquisition, processing and data forwarding. Provides data interfaces within or outside the system for system management, maintenance, and analysis.

UPS: Ensure the normal power supply of the computer monitoring system. When the power supply problem occurs in the entire system, ensure the normal operation of the station control and management equipment.

2) Network communication layer

Communication medium: The system mainly adopts shielded twisted pair, uses RS485 interface, MODBUS communication protocol to achieve real-time communication between the field device and the host computer.

3) Field device layer

The field device layer is a data acquisition terminal and is mainly an ARCM300-JI residual electrical fire monitoring detector. Can monitor single-channel leakage current, each phase cable temperature signal, each channel has a broken line, short circuit detection function; standard 35mm rail mounting, LCD display; screen retention function, when the leakage fault occurs, the channel display screen temporarily stays, Indicates the value of leakage or over temperature in the channel to facilitate the fault recording of the host computer. With the event storage function, the alarm can record the time, type, and parameter of the alarm, can be recorded according to the alarm , and analyze the power consumption at the site to eliminate Faults are provided on the basis of field bus communication technology, PC management software can always monitor the operation of the scene, timely detection of alarm information. The standard MODBUS protocol can be connected to various standard systems; it has a high degree of integration, networking, a high degree of intelligence, and reasonable operating characteristics .

The distributed I/O controller connected to the fieldbus forms a data acquisition terminal and uploads the collected data to the data center. The measuring instruments are responsible for the most basic data collection tasks. The data they monitor must be complete, accurate and transmitted to the monitoring host in real time. It is convenient for operating personnel to monitor the status of field equipment operation, fault alarms, etc. to effectively prevent the occurrence of fire accidents.

4 system function

This set of PC software Acrel- 6 000 electrical fire system. Mainly has the following function characteristic: The friendly man-machine contact surface, may gather the scene equipment the surplus electric current data and the temperature in real time and the time regularly, and has the warning prompt sound and light alarm and so on the function. The customer can set the alarm temperature value and leakage current value according to actual needs. When the alarm fault is removed, it can be reset remotely. The system can record alarm events, dates, alarm values, and over-line values ​​and generate reports that can print alarm event records.

1) fault information prompt

When the monitoring device detects a device failure, the monitoring device will issue the following information:

l The failure unit on the main screen of running monitoring displays a yellow background;

l Operation monitoring The main interface displays real-time fault information. The information content includes: time, device location, device number, and fault information (the display interface is as shown in the figure below);

l In the "Real-time information display area", "fault information" is displayed in red.

l The yellow fault indicator of the monitoring device is on and a fault tone sounds.

2) alarm information and reset

When the monitoring device detects an alarm, the monitoring device will issue the following information:

l The alarm unit on the main screen of the operation monitor displays a red background;

l Operation monitoring The main interface displays real-time alarm information. The information includes: time, equipment location, equipment number, alarm information;

l In the "Real-time information display area", "Alarm information" is displayed in red.

l alarm control output terminal output alarm signal;

l The red alarm indicator of the monitoring device is on and an alarm sounds.

3) Alarm record query

By clicking "Alarm Log Query" under the [Data] menu, enter the alarm record (action information query) screen as shown in the figure below. The user can query the corresponding alarm or the record under the action type in any period within the interface. The operation mode is to select the start date, end date, and query type and click the query button.

4) Port Management

This management function can only be operated by "system management level".

After the “System Management Level” permission is logged in to the system, you can enter the port management interface as shown in the following figure by clicking “Port Management” under the [Maintenance] menu. This interface can modify the corresponding communication port, communication speed and usage status of each channel.

5 Concluding remarks

With the development of smart buildings and the widespread use of electricity, people have become more aware of security awareness. The installation of leakage current fire system in public buildings is an inevitable trend of intelligent construction. The electrical fire system is conducive to discovering hidden dangers and dealing with safety hazards in a timely manner. It is of great significance to prevent fires from occurring.

references

[1]. Ren Chengcheng, Zhou Zhong. Principles and Application Guide for Digital Meters for Electric Power Measurement [M]. Beijing. China Electric Power Press, 2007. 4

[2].Zhou Zhong. Application of Power Meters in Energy Metering of Large-scale Public Buildings [J]. Modern Building Electronics 2010. 6